X1 Improvement information

Date of Release 2026/10/15

◆HMI Program
No. Item Description Version Date
26A0L01 Splash screen Fixed the defect: When a PNG file with the same resolution as the V10 series unit is registered, the right and bottom of the image is clipped by 1 dot. 2.400 2026/10/15
26A0L02 CSV/backup Fixed the defect: When [CSV/Backup Setting] for a logging server comprises [Drive for Output] set to [USB] and [Output timing] set to only [Upon storage removal], a CSV file is created when a screen program is transferred. 2.400 2026/10/15
26A0L03 Graphic relay Fixed the defect: When using a graphic relay (“1 Graphic” type, rendering mode “XOR”), if an arrow with the same size and coordinates as an arrow on the base screen is created in the graphic library and this is displayed using the graphic relay, the arrow is displayed deviated from the arrow on the base screen. 2.400 2026/10/15
26A0L04 Comment display Fixed the defect: When the show/hide setting is used for a comment display part, if the screen is changed over while the part is hidden and then the part is displayed by the specified device memory address, the comments are not displayed after the part is hidden and then displayed again. 2.400 2026/10/15
26A0L05 BRIGHT macro command Fixed the defect: When [CSV/Backup Setting] for a logging server comprises [Drive for Output] set to [USB] and [Output timing] set to [Upon storage removal], executing a BRIGHT macro command creates a CSV backup file. 2.400 2026/10/15
26A0L06 Panel meter Fixed the defect: When a negative value (e.g., -100) is set to the device memory for indicating the current value of a panel meter, the displayed value is “---.--” (indicating overflow) instead of “-1.00”. 2.400 2026/10/15


◆Communication Driver
No. Item Description Version Date
26A0M01 SAIA PCD S-BUS (Ethernet) Fixed the defect: When a PLC is connected, the V10 series unit restarts. 1.500 2026/10/15
26A0M02 RS Automation X8 series Fixed the defect: When a BMOV macro is set to transfer 480 words or more of N device memory, a communication error (time-out) occurs. X8_Xnet,tpf: 1.520
X8_Xnet_E.tpf: 1.510
2026/10/15
26A0M03 Ethernet type drivers Fixed the defect: When a communication error occurs with [Comm. Error Handling] set to [Disconnect] and [Use KeepAlive] set to [Yes], the V10 series unit may freeze or restart.
<Scope> Ethernet type drivers provideed with the following versions:
- V-SFT V6.2.11.0, Smart Editor V1.1.4.0 (released April 2026)
- V-SFT V6.2.11.0a, Smart Editor V1.1.4.0a (released June 2026)
- 2026/10/15
For details on the update procedure,
please refer to the instructions included in the downloaded update module.