| TELLUS Ver. 5 |
| Ver.5.0.4.0 → Ver.5.0.5.0 | Date of Release | 2026/5/11 |
| No. | Item | Description | Altered Ver. |
Correction Ver. |
|---|---|---|---|---|
| 2650X01 | Trend sampling | Fixed defect: The deviation between the scale lines and the graph lines grows larger when scaling in the Y direction. | - | 5.0.5.0 |
| 2650X02 | Vulnerability | Resolved a privilege escalation issue that allowed a standard user to gain administrator privileges during the installation of TELLUS and V-Server. (Reported Vulnerability: ICS-VU-652302) | - | 5.0.5.0 |
| 2650X03 | Ethernet UDP communication |
Fixed the defect: In Ethernet UDP communication with a PLC, if the PLC starts slowly compared to the TELLUS, a screen change using the read area “N+2” may result in the screen before switching and after switching being displayed repeatedly. | - | 5.0.5.0 |
| 2650X04 | Transition | “SYS(SET_SCRN)” macro command Fixed the defect: The screen may not changeover when no transition (F1+1=FFFF) is specified. | - | 5.0.5.0 |
| 2650X05 | Recipes | Fixed the defect: When a record number or name that does not exist is specified for a global recipe (transfer conditions in recipe settings) or a recipe operator (switch function), the information output device memory “n+1” may not output error information as per the specifications. | - | 5.0.5.0 |
| 2650X06 | Modbus TCP/IP (Ethernet) EXT Format | Fixed the defect: Values of a different address may be read depending on the settings of the screen program. | - | 5.0.5.0 |
| 2650X07 | S7-1200/1500 | Fixed the defect: When using V-SFT-6 (version 6.2.3.0 or later) or Smart Editor (version 1.1.2.0) and a screen program that has imported tags for S7-1200/1500 Optimized Tag (Ethernet ISO TCP) is transferred, an error occurs upon attempts to communicate with the PLC and communication cannot be established. | - | 5.0.5.0 |
| 2650Y01 | All drivers | Fixed the defect: When [Comm. Error Handling] is set to [Disconnect] and the TELLUS is used for a long time with the status bar displayed, a reboot may occur. | - | 5.0.5.0 |
| TELLUS Ver. 4 / Ver. 3 |
| Ver.4.0.25.0 → Ver.4.0.26.0 | Date of Release | 2026/5/11 |
| No. | Item | Description | Altered Ver. |
Correction Ver. |
|---|---|---|---|---|
| 2650Q01 | Trend sampling | Fixed defect: The deviation between the scale lines and the graph lines grows larger when scaling in the Y direction. | - | 4.0.26.0 |
| 2650Q02 | Vulnerability | Resolved a privilege escalation issue that allowed a standard user to gain administrator privileges during the installation of TELLUS and V-Server. (Reported Vulnerability: ICS-VU-652302) | - | 4.0.26.0 |
| 2650Q03 | Ethernet UDP communication |
Fixed the defect: In Ethernet UDP communication with a PLC, if the PLC starts slowly compared to the V10 series unit, a screen change using the read area “N+2” may result in the screen before switching and after switching being displayed repeatedly. | - | 4.0.26.0 |
| 2650Q04 | Transition | “SYS(SET_SCRN)” macro command Fixed the defect: The screen may not changeover when no transition (F1+1=FFFF) is specified. | - | 4.0.26.0 |
| 2650Q05 | Recipes | Fixed the defect: When a record number or name that does not exist is specified for a global recipe (transfer conditions in recipe settings) or a recipe operator (switch function), the information output device memory “n+1” may not output error information as per the specifications. | - | 4.0.26.0 |
| 2650Q06 | Modbus TCP/IP (Ethernet) EXT Format | Fixed the defect: Values of a different address may be read depending on the settings of the screen program. | - | 4.0.26.0 |
| 2650R01 | All drivers | Fixed the defect: When [Comm. Error Handling] is set to [Disconnect] and the TELLUS is used for a long time with the status bar displayed, a reboot may occur. | - | 4.0.26.0 |
| V-Server |
| Ver.5.0.2.0 → Ver.5.0.3.0 | Date of Release | 2025/11/4 |
| No. | Item | Description | Altered Ver. |
Correction Ver. |
|---|---|---|---|---|
| 25B0S01 | Loading recipes | Fixed the defect: V-Server may be forcibly terminated if loading of a recipe is executed using an Excel file containing an error in a cell. | 5.0.3.0 |